Perkins 4000 Series 4012-46TAG2A Diesel Engine Technical Data

Oct. 18, 2019

Research shows that Perkins team returns to Middle East Electricity (MEE) in 2017 to promote the full range of its diesel and gas electric power engines. Perkins 4000 Series has a high performance range from 6 to 16 cylinders, with exceptional power-to-weight ratios and a compact design, which makes it easy to transport, install and maintain. Every year, Perkins sells hundreds of 4000 Series engines into the prime power market. From the sentence below, you will see how powerful Perkins 4000 Series engines are!

“Today the 4000 Series is all about quality and reliability. Not just for standby, but for prime. Where quality and reliability are paramount, you can depend on the Perkins 4000 Series to keep the power on… permanently.”


4012-46TAG2A, as one of models of Perkins 4000 Series diesel engine, you will learn its technical data in this article.


General installation


4012-46TAG2A - Temperate


Designation

Units

Type of operation and application

Baseload power

Prime power

Standby power

Gross   engine power

kWm

1069

1331

1459

Fan and   battery charging alternator

power

kW

42

Nett   engine power

kWm

1027

1289

1417

Brake mean   effective pressure (gross)

kPa

1861

2317

 

2538

Combustion   air flow at ISO conditions

m³/min

90

105

120

Exhaust   gas temperature (max) after

turbo

°C

500

Exhaust   gas flow (max) @ atmospheric

pressure

m³/min

309

Boost   pressure ratio

-

2.8

3.4

3.6

Mechanical   efficiency

%

89

91

92

Overall   thermal efficiency (nett)

%

39.5

38.8

38.6

Friction   power and pumping losses

kWm

120

Mean   piston speed

m/s

9.5

Engine   coolant flow

l/min

1020

Typical   Genset electrical output (0.8pf)

kVA

1220

1531

1682

kWe

976

1225

1346

Assumed   alternator efficiency

%

 

95

 

4012-46TAG2A - Tropical


Note: Other parameters are the same to the above Temperate parameters except for these data in the table.


Designation

Units

Type of operation and application

Baseload power

Prime power

Standby power

Fan and   battery charging alternator

power

kW

64

Nett   engine power

kWm

1005

1267

1395

Typical   Genset electrical output (0.8pf)

kVA

1194

1505

1656

kWe

955

1204

1325

 

Energy balance

 

4012-46TAG2A – Temperate


Designation

Units

Baseload power

Prime power

Standby power

Energy

in fuel

KW

2548

3320

3740

in power output (gross)

1069

1331

1459

to cooling fan

42

in power output (nett)

1027

1289

1417

to exhaust

805

1160

1250

to coolant and oil

387

428

499

to radiation

76

100

112

to charge coolers

210

301

420

 

4012-46TAG2A – Tropical:The data is the same to Temperate only difference between energy to cooling fan (64) and energy in power output(baseload power – 1005, prime power – 1267, standby power – 1395).

 

Maximum additional restriction (duct allowance) to   cooling airflow and resultant minimum airflow


Ambient clearance: 50% Glycol

Duct allowance (Pa)

Min airflow

4012-46TAG2A   –

Temperate,

Standby power

35

250

20.2

Tropical, Standby 

power

50

200

32.4

 

Lubricating system


Recommended SAE viscosity: A multigrade oil confirming to the following must be used: API CH4 15W/40.

Note: For additional notes on lubricating oil specifications, please refer to the Operation and Maintenance Manual (OMM).


Lubricating oil capacity

Total system capacity

177 litres

Sump maximum

157.5 litres

Sump minimum

115 litres

Oil temperature at normal operating conditions to   bearings

105

Lubrication oil pressure

At rated speed

400 kPa

Minimum at 80

340 kPa

Oil relief values open

400kPa

Oil filter spacing

20 microns

Sump drain plug tapping size

G1

Oil pump speed

2100 rev.min

Method of drive

gear

Shutdown switch pressure setting (where fitted)

193kPa failing

Oil pump flow

6.0 litres/sec

Normal operating angles

Front and rear

5°

Side tilt

10°

Oil consumption

After running in (typically after 250 hours)

0.52 g/KWhr

Oil flow rate from pump

6 litres/sec

 

Electrical System

Type

Insulated return

Alternator voltage

24 volts with integral regulator

Alternator output

40 amps stabilished, 28 volts at 20 ambient

Starter type

axial

Starter motor voltage

24 volts

Starter motor power

16.4 KW

Number of teeth on flywheel

156

Number of teeth on starter pinion

12

Minimum cranking speed

120 rev/min

Pull in current of starter motor solenoid @ -25 max (1)

30 amps at 24 volts

Holding in current of starter motor soleniod @ -25 max (1)

9 amps at 24 volts

Stop solenoid hold-in current

1,1 amps at 24 volts

Fuel system

Recommended fuel to conform to: BS2869 1998 Class A2 or BS EN590

Injection system

direct

Fuel injection pump and injector type

combined unit injector

Injector pressure

140 MPa

Lift pump type

Tuthill TCH 1-089

Delivery

4012-46TAG1A

1020 litres/hour

4012-46TAG2A

Heat retained in fuel to tank

8 kW

Fuel inlet temperature to be less than

58 °C


Delivery pressure

300 kPa

Maximum suction head at pump inlet

2,5 m

Fuel filter spacing

10 microns

Governor type

electronic


Governing  to ISO 8528-12 CLASS 3 and 4; ISO 8528-5 CLASS G2

Tolerance on fuel consumption

5%


Fuel consumption


                           4012-46TAG2A, Temperate & Tropical

Standby

209

378

Prime

207

342

Baseload

207

270

75% Prime

208

252

50% Prime

212

178

 

Induction system

Maximum air intake restriction of engine:

-clean filter

2 kPa

-dirty filter

4 kPa

-air filter type

paper element

Exhaust system

Exhaust outlet size (internal)

2 x 254 mmTable D flanges

Exhaust outlet flange size

2 x 254 mmTable D flanges

Back pressure for total system at standby power

5 kPa

Engine mounting

Maximum static bending moment at rear face of block

1356 Nm

Maximum additional load applied to flywheel

due to all rotating components

850 kg

Centre of gravity

Bare engine, dry

-forward of the rear face of the cylinder block

771 mm

-above the crankshaft centre line .

32 mm

ElectropaK, dry

-forward of the rear face of the cylinder block

1176 mm

-above the crankshaft centre line

32 mm

 

Cold start recommendations


Temperature  

range


5 °C down   to

-10 °C

(41 °F to

14 °F)

 

Oil :

15W40 CH4

Starter:

2 x 24 volts

Battery:

4 x 12V 286 Ah

Max breakaway current:

1600 amps

Cranking current:

810 amps

Aids:

block heaters

Min mean cranking speed:

120 rev/min

 

Notes:

● The battery capacity is defined by the 20 hour rate

● z The oil specification should be for the minimum ambient

temperature as the oil will not be warmed by the immersion

heater

● Breakaway current is dependant on battery capacity available.

Cables should be capable of handling the transient current

which may be up to double the steady cranking current.

 

4012-46TAG1A / 4012-46TAG2A Temperate - Plan view of support pads, exhaust outlet flange and flywheel


4012-46TAG2A.jpg


Perkins diesel engine 4012-46TAG2A.jpg


4012-46TAG1A / 4012-46TAG2A Tropical - Plan view of support pads, exhaust outlet flange and flywheel


Perkins engine 4012-46TAG1A.jpg



Perkins engine 4012-46TAG2A tropical.jpg


d(B)ATypical load acceptance (cold)



Initial Load Acceptance 

When engine reaches rated speed

(15 seconds maximum after engine 

starts to crank)

2nd Load Application Immediately after engine has recovered to rated speed

(5 seconds after initial load application)

Engine   type

Prime

power%

Load kWe

Nett

Transient

frequency

deviation

%

Frequency

recovery

time

seconds

Prime

power%

Load kWe

Nett

Transient

frequency

deviation

%

Frequency

recovery

time

seconds

4012-46TAG1A

73

800

10

5

27

291

10

5

4012-46TAG2A

71

860

10

5

29

344

10

5

 

The above figures were obtained under test conditions as follows:


Engine block temperature

40 °C

Ambient temperature

25 °C

Governing mode

Isochronous

Alternato inertia

50 kgm²

Under frequency roll off (UFRO) point set to

49,5

UFRO rate set to

16 v/hz

LAM on/off

on

 

Emissions chart


Spill timing 12°

Rating

German TA[1]Luft   @ <3 MW

German TA[1]Luft   Limit @ >3 MW

French   limits

2000 @   <500

hours/year

French   limits

1500 @   >500

hours/year

 

4012-46TAG1A

Baseload

Yes

No

Prime power

Yes

No

Standby

N/A

Yes

No

4012-46TAG2A

Baseload

Yes

No

Prime power

N/A

Yes

No

Standby

N/A

Yes

No

 

German TA Luft legislation (1986) limits:

● NOx ≤ 2000 mg/Nm³

● CO ≤ 650 mg/Nm³

● HC ≤ 150 mg/Nm³

● PM ≤ 50 mg/Nm³

All tests were conducted using an engine installed and serviced to Perkins Engines Company Limited recommendations.

Applied load is a percentage of generator electrical output efficiency as published in the general installation section of this data sheet.

The above data complies with the requirements of classifications 3 and 4 of ISO 8528-/2 and G2 Operating Limits stated in ISO 8528-5.

The information given on this Technical Data Sheet is for standard engines, and for guidance only. For ratings other than those shown contact Perkins Engines Company Limited, Stafford.

Contact Us

  • Add.: No. 10 Kechuang Road, High tech Zone, Nanning, Guangxi, China
  • Tel.: +86 771 5805 269
  • Fax: +86 771 5805 259
  • Cellphone: +86 134 8102 4441
                    +86 138 7819 8542
  • E-mail: sales@dieselgeneratortech.com
Follow Us

Copyright © Guangxi Dingbo Generator Set Manufacturing Co., Ltd. All Rights Reserved | Sitemap

Update cookies preferences
Contact Us