Home Products News Contact Us
Home > Supports > Diesel Engine > Maintenance Process of Diesel Generator Set Distribution Cabinet 2

Maintenance Process of Diesel Generator Set Distribution Cabinet 2

Mar. 06, 2025

This article continues to introduce the maintenance process of diesel generator distribution cabinets.


diesel generator controller


When maintaining the capacitor cabinet, first disconnect the main switch of the capacitor cabinet. Discharge each capacitor to the ground one by one with a wire larger than 25 mm². Then check and tighten the wiring screws of the contactor, reactor, and capacitor. Check whether the grounding device is in good condition. Check whether there is any swelling of the capacitors, and clean the dust inside the cabinet with a vacuum cleaner. After the maintenance is completed, clean up the tools and evacuate the site. Use a 500V megger to measure the insulation resistance between busbars and between busbars and the ground, which should be above 0.5 MΩ.

 

Maintenance of the Distribution Cabinet of Diesel Generator Set - Commissioning

 

Disconnect the grounding switch on the high-voltage side of the transformer. After confirming the disconnection position, close the load switch on the high-voltage side of the transformer. Observe whether the transformer of the diesel generator set operates normally under no-load conditions. Then lock the high-voltage cabinet with a lock and remove the sign. Close the low-voltage side air switches step by step and check whether the low-voltage distribution cabinet is working properly.

 

Safety Precautions for the Maintenance of the Distribution Cabinet of Diesel Generator Set

 

1. Test for electricity after the power outage.

2. When maintaining the distribution cabinet in sections, install an isolation device at the junction of the live and non-live distribution cabinets.

3. When operating the vacuum circuit breaker on the high-voltage side, wear insulating boots and gloves and have a dedicated person for supervision.

4. When maintaining the capacitor cabinet, do not touch it before discharging the capacitors to the ground.

5. Before energizing after the maintenance is completed, first check whether there are any tools left inside the distribution cabinet.

 

Relevant Documents and Records for the Maintenance of the Distribution Cabinet of Diesel Generator Set

 

1. High-voltage operation ticket;

2. Annual maintenance records of the distribution cabinet and transformer;

3. Equipment maintenance records. Records for the maintenance of low-voltage power distribution equipment during power outages of power supply and distribution equipment, operation ticket forms, shift handover records.

 

The above is the maintenance process of the distribution cabinet of the diesel generator set. Hope it is helpful to you.

 

Dingbo Power has advanced testing equipment, modern production technology, professional manufacturing technology, perfect quality management system, and strong technical research and development capabilities. It can provide 3KW~2500KW various specifications of ordinary, automatic, four protection, automatic switching, low noise and mobile generator sets, high quality and low energy consumption to meet the diverse power needs of customers, and can also meet users with different voltages and different frequencies. It is required to create a parallel power supply system for multiple units. If you are interested in our product or any question on generator, welcome to send email to [email protected].

Contact Us

  • Add.: No. 10 Kechuang Road, High tech Zone, Nanning, Guangxi, China
  • Tel.: +86 771 5805 269
  • Fax: +86 771 5805 259
  • Cellphone: +86 134 8102 4441
                    +86 138 7819 8542
  • E-mail: [email protected]
Follow Us

Copyright © Guangxi Dingbo Generator Set Manufacturing Co., Ltd. All Rights Reserved | Sitemap

Update cookies preferences
Contact Us