Home Products News Contact Us
Home > Supports > Diesel Generators > Analysis on Safety Strategy of Diesel Generator Set

Analysis on Safety Strategy of Diesel Generator Set

Dec. 08, 2018

There are many factors that can be affected during the start-up and operation of a diesel generator. If any of these problems occur due to the influence of these factors, it will cause the diesel generator to fail to start and operate normally, causing serious power outages. In order to ensure that the diesel generator set can be started and operated normally and in a timely manner under various harsh environmental conditions, various factors affecting the start-up and operation of the diesel generator set must be analyzed and processed.


Analysis on Safety Strategy of Diesel Generator Set.jpg



 

1. Strict temperature requirements

 

The number on the diesel generator represents its frost resistance. It is generally required to use diesel of -10 or even -30 in winter, and it is enough to use diesel No. 0 in summer. Cold filter points and condensation points are the two main indicators used to measure diesel antifreeze performance. Among them, the unit's condensation point refers to the lowest temperature at which diesel can maintain fluidity under low temperature conditions. This indicator will mainly affect the storage and transportation of diesel; the cold filter point means that diesel does not pass through the engine fuel supply system. The lowest temperature that will cause the filter to clog, and the fuel supply index of the diesel engine will be directly affected by it.

 

2. Strategy to ensure unit startup temperature

 

The temperature of the diesel oil should not be lower than 4 ° C. In other words, it is necessary to ensure that the ambient temperature of the diesel generator set in the standby state cannot be lower than 4 ° C. Only in this way can the diesel generator set start normally. This requires that when the diesel generator set is in standby state, if the ambient temperature is lower than 4 °C, the surrounding air needs to be heated and insulated.

 

3. Ensure the maintenance and maintenance of diesel generator battery

 

As a backup power source, diesel generator sets are not often used in daily situations. The maintenance and maintenance of batteries is a key determinant of the timely start-up of diesel generator sets. The staff should take a series of improvement measures for the maintenance and maintenance of the battery of the diesel generator set. First, the electrolyte and current of the battery should be checked regularly on time. If the electrolyte is found to be missing, the electrolyte should be replenished in time. When the current is found to be insufficient. The battery should be replaced immediately; secondly, the voltage of the battery should be charged in time. This step can be realized by using a full smart charger. When the voltage of the battery is lower than 24V, the battery is charged in time to replenish the battery to the required value. This ensures that the voltage of the battery meets the voltage requirement of 24V at any time, thus providing a safe precondition for the diesel generator set to be reliably started and operated.

 

We should continue to improve the detection and maintenance mechanism of diesel generator sets through research, and constantly improve the safety and stability of the equipment to ensure the safe operation of diesel generator sets.

 

Which parts and precautions should be tested while the diesel engine is running

 

In order to ensure the normal operation of the diesel generator set and extend the service life of the unit, the precautions for the operation of the diesel engine are as follows:

 

1. Never allow the diesel engine to run at full speed before the diesel engine is fully warmed up.

 

2. Do not disconnect the battery or electrode terminals or cables

 

3. During operation, if the battery indicator flashes suddenly, stop immediately and eliminate the malfunction of the electrical system.

 

4. If the exhaust color, sound, and odor are abnormal, stop the machine immediately.

 

5. Running detection

Oil pressure: (90 ~ 300) kPa [(0 9 ~ 3.O) kg / cm2]

(300-650) kPa [(3.0-6 5) kg/cm2 at full load]

Cooling water temperature: Under normal working conditions, the cooling water temperature should be about 80 ° C to 95 ° C.

 

6. Diesel engine operation in winter, pay special attention to cooling water freezing and oil viscosity

 

7. Antifreeze is recommended. When antifreeze is not used, all cooling water should be drained after the diesel engine is running.

 

8. As a result of excessive cooling, thermal efficiency is reduced and fuel consumption is increased. If the cooling water temperature does not reach normal conditions (80-95 ° C) after continuous operation, check the thermostat and other cooling lines.

 

9. Inspection of diesel engine after long-term operation

 

In order to ensure that the diesel engine is always operating under good economic conditions, a thorough inspection and adjustment of the diesel engine should be carried out every year (preferred spring). Parts that affect performance should be checked and adjusted:

 

Intake and exhaust components: air filter, buffer, supercharger, etc.

Lubrication and cooling components: oil cooler, oil filter, antifreeze, etc.

Gas distribution and fuel components: valve clearance, diesel filter, etc.

 

After the diesel engine is running at full load, before stopping, the diesel engine's speed controller should be switched to idle speed and run for about 5 minutes, so that the diesel engine can be gradually and evenly cooled down, and the cooling water can be stopped after the temperature drops to 60 °C.

 


Contact Us

  • Add.: No. 10 Kechuang Road, High tech Zone, Nanning, Guangxi, China
  • Tel.: +86 771 5805 269
  • Fax: +86 771 5805 259
  • Cellphone: +86 134 8102 4441
                    +86 138 7819 8542
  • E-mail: sales@dieselgeneratortech.com
Follow Us

Copyright © Guangxi Dingbo Generator Set Manufacturing Co., Ltd. All Rights Reserved | Sitemap

Update cookies preferences
Contact Us