This article will guide you to learn about Baudouin power generation product characteristics and applications.
Baudouin products | Competitive products |
M26/33 (Special purpose) | KTA19 KTA38 KTA50 |
M33 | QSK19 QSK38 QSK50 |
M55 | M4000 QSL60 QSK78 QSK95 |
Wide power range
Good economy
Pre-filtered air filter: greatly extend the maintenance and replacement cycle of the air filter element
Three-level babysitter filter: fuel filter replacement cycle up to 400h
Centrifugal rotor filter: oil filter replacement cycle up to 400h
Fuel consumption rate is better than competing products
High reliability
Body, cylinder head, crankshaft and connecting rod:
High-strength design, improve the reliability of the whole machine, long overhaul period
Overhaul period: design life 32000h
Good NVH performance
Injection molding air filter: light weight, reduce engine vibration
Casting oil pan: high strength, reduce vibration noise
Easy to start at low temperature
High compression ratio: effectively increase the compression termination temperature.
Electric fuel pump: automatic emptying can be realized.
Intake heating device: ensure normal starting of engine at-20℃
Baudouin 6M33D starts smoothly at -20°C without other preheating devices.
6M33D is equipped with water boiler and oil heating rod, which starts smoothly at-41 ±2℃.
Good plateau adaptability
1. Supercharger selection: engine development takes into account plateau performance;
2. ECU automatically adjusts the fuel supply advance angle;
3. CAE simulation: simulation of plateau conditions for calculation and analysis;
4. Three-high test: the performance of diesel engine was checked at high altitude.
Altitude | Ambient temperature (℃) | Engine power (kw) | Engine power drop |
0m | 30 | 1264.1 | 0 |
20 | 1270.3 | 0 | |
1000m | 25 | 1274.6 | 0 |
20 | 1278 | 0 | |
2000m | 20 | 1261.6 | 0 |
15 | 1273.1 | 0 | |
3000m | 15 | 1191 | 3.9% |
10 | 1191.7 | 3.8% | |
4000m | 10 | 1110.2 | 10.4% |
5 | 1102.4 | 11% | |
5000m | 5 | 1038 | 16.2% |
0 | 1030.8 | 16.8% | |
6000m | 0 | 950 | 23.3% |
-5 | 945.1 | 23.7% |
Baudouin Diesel Generator Set Applications
1. 12M26 land power model matching national power grid emergency power supply vehicle.
Model | Genset Power |
12M26D968E200 | Standby 880KW |
2. 12M33 Land-electric type matching oil drilling platform generator set (use location: Loess Plateau)
Model | Genset Power |
12M33D1210E200 | Rated 1000KW |
For windy sand and dust environment, Weichai has developed a special desert air filter, which can ensure the use of diesel engine in this environment.
3. 12M55 land power generator supporting China Unicom data center backup power supply.
Model | Unit Power |
12M55D2175E310 | Stand by 2MW |
4. 6M26 land power generation model matching armed police emergency power supply vehicle.
Model | Unit Power |
6M26D484E200 | Stand by 400KW |
Since the launch of the market, Baudouin products have won the unanimous approval of the users with its excellent quality, performance and high-end configuration, and have been favored by the armed police and other departments.
The engine power is defined as follows:
Prime rated power (PRP):
1. The annual running time is not limited;
2. The average load rate should not exceed 70% for each 250h duration;
3. Run no more than 500h per year under 100% load;
4. Within 12h, it can be overloaded for 10% for 1h, and the accumulated overload operation for no more than 25h per year.
Emergency standby power (ESP):
1. The annual running time does not exceed 200h, including no more than 25h per year under 100% load;
2. The average load rate does not exceed 80% every 24h operation cycle;
3. Does not have overload capacity.
Starlight Power can provide 400KW to 3000KW prime & emergency standby diesel power generators with Baudouin engine. (China Non-Road Emission Stage III standard.) If you are interested, contact us by email: [email protected].